Current Carrying Capacity of Copper Conductors

The current carrying capacity refers to the maximum amount of electric current a conductor can safely handle without causing damage to itself or its insulation. This capacity is influenced by several factors, including the heat generated by the current and the temperature limits of the surrounding environment. The ability of a copper conductor to carry current depends on how much heat it can dissipate before reaching critical levels that could cause melting or degradation of its properties.

Table of contents

  • Key Determinants of Current Carrying Capacity of Copper Conductors
  • Annealed Bare Copper Wire Specification
  • Bundled Conductors Derating Factors
  • Formula for The Current Carrying Capacity
  • Current Calculation Formula
  • Copper Conductor Ampacity Charts
  • Current Carrying Capacity of Copper Wire Per sq mm Chart
  • Current Carrying Capacity Of Aluminium Cable
  • Class 2 Copper Wire Diameter Chart & Properties
  • Amperes Conductor Chart
  • Copper Conductor vs Aluminum Conductor
  • Applications of Copper Conductors
  • Copper Conductor Resistance
  • Types of Copper Cable Current Carrying Capacity

Key Determinants of Current Carrying Capacity of Copper Conductors

Factor Details
Conductor Size Larger cross-sectional area allows higher current flow.
Heat Generation The conductor must remain below the maximum temperature rating of its insulation.
Ambient Temperature Higher ambient temperatures reduce the allowable current due to reduced cooling efficiency.
Conductor Number More conductors in close proximity lead to reduced heat dissipation and lower current capacity.

Annealed Bare Copper Wire is Manufactured as Per IEC 60228 Standard

Annealed bare copper wire undergoes a forming process similar to hard-drawn copper, followed by heat treatment to improve flexibility and workability. This makes the wire more malleable and less prone to breaking under stress. The IEC 60228 standard ensures that the wire meets international quality and performance benchmarks, making it a reliable choice for engineers and electricians.

This standard outlines the requirements for conductors used in insulated cables, ensuring consistent quality and safety across different applications. The following table provides an overview of the properties and uses of annealed bare copper wire.

Annealed Bare Copper Wire Specification

Aspect Details
Essential Properties Excellent electrical conductivity.
Ideal for bending and wrapping.
Long-lasting and robust.
Uses in Industry Binding and winding.
Power transmission.
Industrial applications.
Electroplating processes.
Annealed Bare Copper Wire Manufactured using vacuum furnace heating.
Offers superior conductivity and flexibility.
Adheres to strict manufacturing guidelines.
Quality and Compliance Complies with international standards.
Suitable for both industrial and household use.

Bundled Conductors Derating Factors

Bundle Derating Factor (X Amps)
2-5 0.8
16-30 0.5
6-15 0.7
These charts as a guide for determining conductor and cable current ratings

What methods can be used to find the cable’s current carrying capacity?

Method Description Key Considerations
Ampacity Calculation Calculates the maximum current a cable can carry based on its physical and material properties. Consider factors like cross-section, material, insulation, ambient temperature, and installation method.
Thermal Modeling Estimates the maximum current using heat transfer principles. Focuses on thermal resistance, heat dissipation, and environmental conditions.
Measurement and Monitoring Directly measures the cable’s temperature rise under load. Requires monitoring of temperature and rated operating conditions.
Empirical Data and Standards Relies on industry standards and guidelines for current ratings. Includes NEC, IEC, and other relevant codes.
Simulation and Modeling Software Uses specialized software tools to simulate cable behavior under various conditions. Depends on accurate loading and environmental data inputs.

How much current is a wire capable of carrying?

Factor Description Example
Gauge Thicker wires have higher current capacity due to lower resistance. 14-gauge: up to 15 amps; 12-gauge: up to 20 amps.
Insulation Higher temperature-rated insulation allows greater current capacity. Rated for temperatures like 60°C or 90°C.
Length Longer wires have higher resistance, reducing capacity. Increased length may lower current capacity.
Temperature Higher ambient temperatures decrease safe current limits. Higher temperatures reduce the wire's capacity.

What is copper Conductor current density?

Condition Current Density Description
Standard Conditions 1 to 1.5 A/mm² Typical range for general applications.
High-Temperature Applications Up to 2 A/mm² or more Can be higher depending on cooling and insulation.

Formula for The Current Carrying Capacity

Factor Details
Formula I = K * A / L
I Maximum current load (amps)
K Constant based on material type
A Cross-sectional area (mm²)
L Length (meters)
Example Standard annealed copper wire
Cross-sectional Area 1 mm²
Length 10 meters
K Value 0.0175 Ω/m
Calculation I = 0.0175 * 1 / 10 = 0.00175 amps or 1.75 mA
Result Maximum current load = 1.75 milliamps (mA)

What is the Current Capacity of an Aluminium and Copper Conductor?

Features Aluminum Conductors Copper Conductors
Max Current Density Up to 3.5 A/mm² Up to 3.5 A/mm²
Cooling Medium Essential for heat dissipation; affects capacity. Essential for heat dissipation; affects capacity.
Resistivity Higher resistivity Lower resistivity
Specific Gravity Lower, making it lighter Higher, making it heavier
Current-Carrying Area Requires larger cross-sectional area Requires smaller cross-sectional area

Current Calculation Formula

Details
Formula Current (I) = Voltage (V) / Resistance (R)
Known as Ohm’s Law
Current (I) Measured in Amperes (A)
Voltage (V) Measured in Volts (V)
Resistance (R) Measured in Ohms (Ω)
Relationship Current is directly proportional to Voltage and inversely proportional to Resistance

Benefits of Using Copper Conductors

Benefits Description
Superior Conductivity High electrical conductivity, second only to silver.
Heat Resistance High melting point and heat resistance, ideal for heat-related components.
Corrosion Resistance Good resistance to corrosion, enhancing durability.
Overloading Risk High heat resistance helps reduce the risk of overloading issues.
Versatility Available in various forms (bare, stranded) and compatible with other metals.
Thermal and Electrical Conductivity High thermal and electrical conductivity ensures efficient performance.

Refer Ampacity Charts of Bare Copper Ground Conductor

The ampacity chart provides the maximum current that a bare copper ground conductor can safely carry without exceeding its temperature limit. These charts are essential for engineers and electricians to ensure the safety and reliability of electrical systems.

Copper Conductor Ampacity Charts

Copper (Wire Size & Amp Ratings)
Wire Gauge Size 60°C (140°F)
NM-B, UF-B
75°C (167°F)
THW, THWN,
SE, USE, XHHW
90°C (194°F)
THWN-2, THHN,
XHHW-2, USE-2
14 15 20 25
12 20 25 30
10 30 35 40
8 40 50 55
1 — 130 145
1/0 — 150 170
2/0 — 175 195
3/0 — 200 225
6 55 65 75
4 70 85 95
3 85 100 115
2 95 115 130
4/0 — 230 260
250 — 255 290
300 — 285 320
750 — 475 535
1000 — 545 615
350 — 310 350
500 — 380 430
600 — 420 475

Why is the Size of a Conductor Depending on Its Current?

Aspect Description
Current-Size Relationship The size of a conductor depends on the amount of current it will carry.
Power Loss Loss of power as heat due to resistance, given by P=I²×R.
Resistance and Area Power loss is proportional to the square of the current.
Larger Conductors Required for higher currents to reduce resistance and minimize power loss.
Smaller Conductors Suitable for lower currents as they have lower power loss and resistance.
Safety and Efficiency Larger conductors help prevent overheating

Current Carrying Capacity of Copper Wire Per sq mm Chart

Nominal CrossSection (mm²) Group 1 Group 2 Group 3
Current Carrying Capacity(A) Copper Wire Protective Fuse(A) Current Carrying Capacity(A) Copper Wire Protective Fuse(A) Current Carrying Capacity(A) Copper Wire Protective Fuse(A)
0,75     12 6 15 10
1 11 6 15 10 19 16
1,5 15 10 18 16 24 20
6 33 25 44 32 54 50
10 45 32 61 50 73 63
16 61 50 82 63 98 80
25 83 63 108 80 129 100
2,5 20 16 26 20 32 25
4 25 20 34 25 42 32
35 103 80 135 100 158 125
50 132 100 168 125 198 160
120 235 200 292 250 344 315
150     335 250 391 315
185     382 315 448 400
70 165 125 207 160 245 200
95 197 160 250 200 292 250
240     453 315 528 400
300     504 400 608 500
400         726 630
500         830 630

Current Carrying Capacity Of Aluminium Cable

Current Carrying Capacity Of Aluminium Cable

2.5 Sq MM Cable Specification

Guage Volts Support Amp Load Suitable For
2.5 Sq MM 250 110 500 Watts Normal Load

4.0 Sq MM Cable Details

Guage Volts Support Amp Load Suitable For
4.0 Sq MM 250 110 800 Watts Normal Load

6.0 Sq MM Cable Specification

Guage Volts Support Amp Load Suitable For
6.0 Sq MM 250 110 1200 Watts Normal Load

8.0 Sq MM Cable Load Capacity

Guage Volts Support Amp Load Suitable For
8.0 Sq MM 250 110 1800 Watt Heavy Load

10 Sq MM Cable Load Specification

Guage Volts Support Amp Load Suitable For
10 Sq MM 250 110 2500 Watt Heavy Load

Check Diameter Chart and Properties of Class 2 Copper Wire

Class 2 copper wire is often used in high-temperature environments. It offers better mechanical properties than Class 1 copper wire, including improved ductility and strength. This makes it suitable for applications where moderate mechanical stress is expected while maintaining good conductivity and longevity.

Class 2 Copper Wire Diameter Chart & Properties

NO. OF WIRES NOMINAL CROSSSECTIONAL AREA (mm²) DIAMETER OFCONDUCTORSmm DIAMETER OF WIRES (mm) MECHANICAL PROPERTIES OFPLAIN COPPER WIRE MAXIMUM DCRESISTANCEAT 20°(ohms/km) NOMINALWEIGHT(kg/km)
Minimum Elongation% Minimum TensileStrength(N/mm2)
7 16 4.8 1.74 28 200 1.15 137
7 25 5.8 2.19 28 200 0.727 215
7 1.5 1.59 0.53 24 200 12.1 13
7 10 3.85 1.35 26 200 1.83 87
7 35 6.9 2.62 28 200 0.524 300
10 50 8.2 2.62 28 200 0.387 410
7 2.5 2.01 0.67 24 200 7.41 21
7 4 2.55 0.85 24 200 4.61 35
7 6 3.15 1.05 26 200 3.08 52
14 70 9.7 2.62 28 200 0.268 595
19 95 11.4 2.62 28 200 0.193 820
48 240 18.6 2.62 28 200 0.0754 2100
61 300 20.4 2.62 28 200 0.0601 2700
19 120 13.1 2.62 28 200 0.153 1040
37 150 14.2 2.62 28 200 0.124 1280
37 185 15.8 2.62 28 200 0.0991 1600
61 400 26 3 33 200 0.047 3400
61 500 30 3 33 200 0.0366 4400

Amperes Conductor Chart

Cylinder Bottle

There are many kind of PET bottles, Boston shape, cylinder shape,square shape,abnormal shape.

With PET material and PCR-PET eco-friendly material .

The volume has 10ml 20m 30ml 40ml 50ml 60ml 80ml 100ml 120ml 130ml 150ml 200ml 300ml 400ml 500ml etc

Apply to Lotion Pump Bottle,Foam Pump Bottle,Mist Spray Bottle, Shampoo Bottle packaging ,liquid soap bottle packagingcosmetic packaging.



Cylinder Bottle,Square Lotion Bottle,Pet Square Bottle,Pet Round Bottle

NINGBO CRETE PLASTIC CO.,LTD , https://www.crete-sprayer.com

Posted on
Insulation Materials: Copper Temp. 30 AWG 28 AWG 26 AWG 24 AWG 22 AWG 20 AWG 18 AWG 16 AWG 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG
Polyethylene
Neoprene Polyurethane
Polyvinylchloride (Semi-Rigid)
80°C 2 3 4 6 8 10 15 19 27 36 47 65 95 125 170
Polypropylene Polyethylene(High Density) 90°C 3 4 5 7 9 12 17 22 30 40 55 70 100 135 180
Polyvinylchloride PVC (Irradiated) Nylon 105°C 3 4 5 7 10 13 18 24 33 45 58 75 105 145 200
Kynar (135°C)
Polyethylene(Crosslinked)
Thermoplastic Elastomers
125°C 3 5 6 8 11 14 20 26 40